Description
Cu conductor, PVC insulated, PVC sheath. 0.6/1 kV. Made to AS/NZS 5000.1
Standards
National : AS/NZS 5000.1Description
Application
- Industrial and commercial applications (predominantly)
- Some domestic applications
- For use in various situations to supply the main power from the point of supply (either single or three phase application) to buildings, equipment, eg, switch board to main control cabinet, main between floors and buildings, cable cabinet to motor, etc. Commonly used in Power Authority work.
Characteristics
Construction characteristics | |
---|---|
Sheath colour | White |
Conductor material | Copper |
Type of conductor | Circular, stranded |
Insulation | PVC |
Outer sheath | PVC |
With Green/Yellow core | No |
Insulation colour | White |
With smaller neutral conductor | No |
Dimensional characteristics | |
Conductor cross-section | 25mm² |
Nominal overall diameter | 11.8mm |
Gland Size (A2 or A2F) | 20 |
Approximate weight | 0.35kg/m |
Number of cores | 1 |
Electrical characteristics | |
Max. DC resistance of the conductor at 20°C | 0.727Ohm/km |
Permissible short circuit current conductor 1s | 2.8kA |
Rated Voltage Uo/U (Um) | 0.6/ 1 (1.2) kV |
Mechanical characteristics | |
Cable flexibility | Rigid |
Usage characteristics | |
Max. conductor temperature in service | 75°C |
Docs and info
Current carrying capacities single phase (in Amps) - Single conductor PVC |
Copper conductor - Circular stranded - Insulation PVC Aluminum conductor - Circular stranded except 240 mm² Compact circular stranded - Insulation PVC Max. Conductor Temperature 75⁰C |
![]() |
Air Spaced from Surface, Unenclosed | 76 |
![]() |
Air touching, unenclosed | 62 | |
![]() |
Air enclosed | 62 |
![]() |
Buried direct | 94 | |
![]() |
Buried in single-way duct | 142 |
![]() |
Buried in multi-way duct | 128 | |
![]() |
Cable surrounded by thermal insulation, unenclosed | 55 |
Current carrying capacities three phase (in Amps) - Single conductor PVC |
Single Conductor PVC (three phase) PVC insulation Unarmoured Sheathed or unsheathed For cables up to and including 0.6/1 kV @ 50 Hz AC. |
![]() |
Air Spaced from Surface, Unenclosed | 117 |
![]() |
Air touching, unenclosed | 111 | |
![]() |
Air enclosed | 92 |
![]() |
Buried direct | 147 | |
![]() |
Buried in single-way duct | 129 |
![]() |
Buried in multi-way duct | 110 | |
![]() |
Cable surrounded by thermal insulation, unenclosed | 55 |