PVC Neutral Screened Cables single core and two cores

Description
Cu conductors, PVC insulation, Cu wire neutral screen, Black PVC sheath. 0.6/1 kV. Made to AS/NZS 4961.
Description
Standards
National : AS/NZS 4961Description
Application
- Industrial, commercial and domestic applications
- For use in various situations to supply the main power from the point of supply to buildings, equipment, sheds, eg, switch board to main control cabinet, main between floors and buildings, cable cabinet to motor, etc.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Type of conductor | Circular, stranded |
Insulation | PVC |
Screen | Copper wire |
Outer sheath | PVC |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/ 1 (1.2) kV |
Usage characteristics | |
Max. conductor temperature in service | 75°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Core Colours
No. of Cores |
Colour |
1 |
RD |
1 (Plus Pilot) |
RD, OG |
2 |
RD, WH |
2 (Plus Pilot) |
RD, WH, OG |
3 |
RD, WH, BU |
4 |
RD, WH, BU, BK |
Current carrying capacities single phase (in Amps) - PVC neutral single core
- Copper conductor
- Circular stranded
- Insulation PVC
- Max. Conductor Temperature 75⁰C
-
- Air Spaced from Surface, Unenclosed
-
- Air touching, unenclosed
-
- Air enclosed
-
- Buried direct
-
- Buried in single-way duct
-
- Cable surrounded by thermal insulation, unenclosed
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu |
4 | 42 | 39 | 34 | 43 | 43 | 19 |
6 | 52 | 50 | 44 | 55 | 55 | 25 |
10 | 73 | 68 | 59 | 73 | 73 | 34 |
16 | 97 | 91 | 78 | 125 | 95 | 46 |
25 | 129 | 122 | 103 | 162 | 123 | 60 |
35 | 158 | 149 | 128 | 196 | 150 | 74 |
50 | 194 | 181 | 152 | 232 | 178 | - |
Current carrying capacities single phase (in Amps) - Two core PVC neutral
- Copper conductor
- Circular stranded
- Insulation PVC
- Max. Conductor Temperature 75⁰C
-
- Air Spaced from Surface, Unenclosed
-
- Air touching, unenclosed
-
- Air enclosed
-
- Buried direct
-
- Buried in single-way duct
-
- Cable surrounded by thermal insulation, unenclosed
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu |
2.5 | 26 | 25 | 23 | 28 | 28 | 13 |
4 | 35 | 33 | 29 | 36 | 36 | 17 |
6 | 46 | 42 | 38 | 46 | 46 | 22 |
10 | 62 | 58 | 50 | 61 | 61 | 29 |
16 | 82 | 78 | 66 | 106 | 80 | 39 |
25 | 111 | 104 | 87 | 138 | 103 | 52 |
35 | 137 | 128 | 107 | 165 | 125 | 64 |