Cu Aerial - Neutral Screen

Description
Hard drawn copper conductor, PVC insulation, Copper Neutral Screen, PVC Sheath. Made to ASNZS 4961.
Description
Standards
National : AS/NZS 4961Description
Can be used for aerial reticulation to residential and rural areas where reliability, safety and low installation costs are required.
It is also designed for residential and rural areas for reducing the bushfire hazards.
The covering contains a high level of carbon black for UV resistance.
It is designed for where reliability, safety and low installation costs are required, but it is only for short spans due to increased weight.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Insulation | PVC |
Screen | Copper wire |
Outer sheath | PVC |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/ 1 (1.2) kV |
Usage characteristics | |
Maximum operating temperature | 75°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Electrical Performance Data - Single Core (with or without pilot)
Conductor |
Calculated DC |
Maximum AC |
Current Rating |
Current Rating |
6 |
3.17 |
3.86 |
34 |
57 |
16 |
1.18 |
1.44 |
59 |
103 |
Electrical Performance Data - Two Core (with or without pilot)
Conductor |
Calculated DC |
Maximum AC |
Current Rating |
Current Rating |
16 |
1.18 |
1.44 |
54 |
97 |
Electrical Performance Data - Three Core (with or without pilot)
Conductor |
Calculated DC |
Maximum AC |
Current Rating |
Current Rating |
6 |
3.17 |
3.86 |
30 |
55 |
10 |
1.88 |
2.29 |
41 |
74 |
16 |
1.18 |
1.44 |
54 |
97 |
-
Note
- Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under Copyright Licence 000926. Please see the Standard for full details.
- Current ratings are based on an ambient temperature of 30°C, a maximum conductor temperature of 75°C, summer noon and intensity of solar radiation 1000 W/m².