Remolex Cables

Description
Cu Conductors, PVC insulation, Laid up, Black PVC sheath, 450/750 V. Made to AS/NZS 5000.2. Circular multicore with integral earth.
Description
Standards
National : AS/NZS 5000.2Description
Application
- Industrial, commercial and domestic applications
- Small mains cables.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Type of conductor | Circular, stranded |
Insulation | PVC |
Outer sheath | PVC |
Electrical characteristics | |
Rated Voltage Uo/U | 450/750 V |
Usage characteristics | |
Max. conductor temperature in service | 75°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Core Colours
No. of Cores |
Colour |
3 |
RD, BK, GNYE |
4 |
RD, WH, BU, GNYE |
5 |
RD, WH, BU, BK, GNYE |
Current carrying capacities single phase (in Amps) - Remolex two cores
- PVC insulation
- Armoured or unarmoured
- For cables up to and including 0.6/1 kV @ 50 Hz AC.
-
- Air touching, unenclosed
-
- Air Spaced from Surface, Unenclosed
-
- Air enclosed
-
- Buried direct
-
- Buried in single-way duct
-
- Cable surrounded by thermal insulation, unenclosed
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu |
1.5 | 22 | 21 | 18 | 23 | 23 | 10 |
2.5 | 31 | 30 | 26 | 33 | 33 | 15 |
4 | 42 | 39 | 34 | 43 | 43 | 19 |
6 | 52 | 50 | 44 | 55 | 55 | 25 |
© Copyright Standards New Zealand 2012.
Content in this table and the typical New Zealand installation conditions are derived from AS/NZS 3008.1.2:2010 and has been reproduced or adapted with permission from Standards New Zealand under Copyright Licence 000926. Please refer to the complete Standard for full details available for purchase from Standards New Zealand at www.standards.co.nz.
The values are for typical New Zealand installation conditions of:
- Ambient Air Temperature:30°C
Current carrying capacities three phase (in Amps) - Three & Four Core Remolex PVC
- Copper conductor
- Circular stranded
- Insulation PVC
- Max. Conductor Temperature 75⁰C
-
- Air Spaced from Surface, Unenclosed
-
- Air touching, unenclosed
-
- Air enclosed
-
- Buried direct
-
- Buried in single-way duct
-
- Cable surrounded by thermal insulation, unenclosed
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu |
1.5 | 18 | 17 | 16 | 20 | 20 | 9 |
2.5 | 26 | 25 | 23 | 28 | 28 | 13 |
4 | 35 | 33 | 29 | 36 | 36 | 17 |
6 | 46 | 42 | 38 | 46 | 46 | 22 |
10 | 62 | 58 | 50 | 61 | 61 | 29 |
16 | 82 | 78 | 66 | 106 | 80 | 39 |
© Copyright Standards New Zealand 2012.
Content in this table and the typical New Zealand installation conditions are derived from AS/NZS 3008.1.2:2010 and has been reproduced or adapted with permission from Standards New Zealand under Copyright Licence 000926. Please refer to the complete Standard for full details available for purchase from Standards New Zealand at www.standards.co.nz.
The values are for typical New Zealand installation conditions of:
- Ambient Air Temperature: 30°C
- Soil Temperature: 15°C
- Soil Thermal Resistivity: 1.2 K.m/W
- Depth of Burial: 0.5 m