TPS - Three Core (Yellow)
Description
Cu conductors, PVC insulation, PVC sheath. 450/750 V. Made to AS/NZS 5000.2
Description
Cu conductors, PVC insulation, PVC sheath. 450/750 V. Made to AS/NZS 5000.2
Standards
National : AS/NZS 5000.2Description
Application
- Domestic, commercial and industrial general applications
- Lighting applications
- Fixed applications
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Insulation | PVC |
Outer sheath | PVC |
Electrical characteristics | |
Rated Voltage Uo/U | 450/750 V |
Usage characteristics | |
Max. conductor temperature in service | 75°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Current carrying capacities (in Amps) - 3 core, 3 core plus earth, 4 core TPS cables three phase
- Copper conductor
- Circular stranded (except 1 mm² which is solid)
- Insulation PVC
- Max. Conductor Temperature 75⁰C
-
- Air Spaced from Surface, Unenclosed
-
- Air touching, unenclosed
-
- Air enclosed
-
- Buried direct
-
- Buried in single-way duct
-
- Cable surrounded by thermal insulation, unenclosed
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu |
1 | 15 | 14 | 13 | 15 | 15 | 7 |
1.5 | 18 | 17 | 16 | 20 | 20 | 9 |
2.5 | 26 | 25 | 23 | 28 | 28 | 13 |
4 | 35 | 33 | 29 | 36 | 36 | 17 |
6 | 46 | 42 | 38 | 46 | 46 | 22 |
Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under Copyright Licence 000926. Please see the Standard for full details.
The values in this table are for typical New Zealand installation conditions of:
- Ambient Air Temperature 30°C