AL URD Cables

Description
Al Conductors, XLPE insulation, Black PVC Sheath, 0.6/1 kV. Made to AS/NZS 4026
Description
Al Conductors, XLPE insulation, Black PVC Sheath, 0.6/1 kV. Made to AS/NZS 4026
Standards
National : AS/NZS 4026Description
Application
- Recommended for use in Underground Residential Distribution Systems.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Aluminum |
Insulation | XLPE |
Outer sheath | PVC |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/ 1 (1.2) kV |
Usage characteristics | |
Max. conductor temperature in service | 90°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Current carrying capacities three phase (in Amps) - AL URD XLPE
- Aluminium conductor
- Shaped stranded
- Insulation XLPE
- Max. Conductor Temperature 90⁰C
-
- Air Spaced from Surface, Unenclosed
-
- Air touching, unenclosed
-
- Air enclosed
-
- Buried direct
-
- Buried in single-way duct
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|
mm² | Al | Al | Al | Al | Al |
50 | 154 | 143 | 116 | 170 | 128 |
70 | 196 | 182 | 147 | 209 | 161 |
95 | 242 | 224 | 178 | 250 | 194 |
120 | 282 | 262 | 211 | 286 | 225 |
185 | 374 | 347 | 276 | 364 | 291 |
240 | 446 | 413 | 333 | 423 | 345 |
300 | 514 | 475 | - | 477 | 391 |